Your cart is empty
The Phoenix Contact OCHRONA VAL-MS-T1/T2 335/12,5/3+1 AC surge protective device Type 1+2 features a maximum discharge current Imax of 50 kA. The device has 4 poles, an IP20 protection degree, and a response time of less than 25 ns.
The Phoenix Contact OCHRONA VAL-MS-T1/T2 335/12,5/3+1 AC surge protective device Type 1+2 is a three-phase device designed for the surge protection of electrical installations. The rated voltage of this component is 240/415 V, and its maximum continuous operating voltage reaches 335 V. The modular design with four poles allows for a safe connection in an alternating current grid. This component is an essential element in building photovoltaic protections that safeguard equipment against the effects of lightning discharges.
| Rated voltage | 240/415 V |
| Maximum continuous operating voltage | 335 V |
| Number of poles | 4 |
| Nominal discharge current In | 12.5 kA |
| Maximum discharge current Imax | 50 kA |
| Voltage protection level Up | ≤ 1.2 kV |
| Response time | ≤ 25 ns |
| Cross-section | 1.5 ... 25 mm² |
| Protection degree | IP20 |
| Operating temperature | -40 ... 80 °C |
| Height | 90 mm |
| Width | 71 mm |
| Depth | 77.5 mm |
| Weight | 0.64 kg |
| Length | 78 mm |
AC surge protective device Type 1+2, 3-Phase, Phoenix, OCHRONA VAL-MS-T1/T2 335/12,5/3+1 — B2B wholesale prices for installers and contractors. Check availability and terms of cooperation: contact us.
B2B
Individual terms, account manager.